Item | remote mount split Air temperature humidity controller transmitter |
Application | air temperature and humidity measure |
Material | ABS plastic |
Output | 4-20mA, 0-10V, RS485 |
Temperature | -40~125C |
Humidity range | 0-100%RH |
Power supply | 24VDC |
Protection | IP65 |
Display | LCD display optional |
Dimensions | 140x100x40mm |
Measuring medium: gas (compatible with contact material)
Overall material: ABS engineering plastic for main shell
Filter (contact) polyethylene (density 50 μ m)
Cable locking head nylon (locking wire diameter 5-8mm)
Display LCD with backlight
Installation flange (contact) ABS engineering plastics
Insert bar (contact) ABS engineering plastics
Seal (contact) NBR / silicone
Temperature range: - 40 ~ 0 ~ 125 ºC (Note 1)
Humidity range: 0-100% RH (relative humidity)
Supply voltage: 24VDC (current / voltage output)
12-24vdc (RS485 output)
Output signal: RS485, 4-20mA, 0-10vdc
Response frequency: ≤ 2Hz
Response speed: 10 ºC for temperature and 10% RH for humidity,
The gas flow rate is 0.1m/s.
Working conditions: ambient temperature - 40 ~ 85 ºC
Ambient humidity 5% - 95% RH (no condensation)
Stability: ± 1% RH FS / year ± 0.2 ºC / year
Seismic performance: 5g (20... 2000Hz)
Overall weight: with display ≈ 187G
No display ≈ 162g
Protection grade: IP65
Power range: with display without display
Current mode ≤0.05Us(W) ≤0.06Us(W)
Digital type ≤0.015Us(W) ≤0.025Us(W)
Voltage type ≤0.015Us(W) ≤0.025Us(W)
Note: US = supply voltage
Load characteristics: current type load ≤ {(us-12) ÷ 0.02 (US =
supply voltage)} Ω Voltage type load ≥ 100k Ω
Details Images remote mount split Air temperature humidity controller transmitter